Actually,
it is rather simple. A DOP generator introduces aerosol as a challenge
agent into the upstream side fo the filter system. A sample of this aerosol-air
mixture is taken on the upstream side of the filter with a linear forward
light scattering photometer for use as a baseline to compare the downstream
readings. since the upstream concentration is known, and the photometer
is linear, the downstream samples may be read out in percent of concentration,
as recommended in the standrds and specifications. Any leak greater than
0.01% of the upstream concentration is too much, and tyhe spot should
be marked for repairs in actuality, there should be no leaks around the
filter seals, and in practice, readings at the face of the filter are
usually in the 0.004% to 0.008% range.